SMART Box device

The SMART Box Tango devices reflect the state of the individual FNSC (Field Node SMART Box Controller) devices, including FEM port power status. The following attributes are exposed; note all attributes are read-only with the exception of the alarm and warning thresholds, and FEM current trip thresholds. All temperatures are in degrees Celsius.

Tango attribute name

Register

address(es)

Register description

ModbusRegisterMapRevisionNumber

1

Modbus FNPC register map revision number, fixed at firmware compile time

PcbRevisionNumber

2

FNCB revision number, fixed at firmware compile time

CpuId

3-4

Microcontroller device ID

ChipId

5-12

Microcontroller unique device ID

FirmwareVersion

13

Firmware revision number, fixed at compile time

Uptime

14-15

Time, in seconds, since FNPC boot

SysAddress

16

Modbus address

InputVoltage

17

Incoming 48Vdc voltage

PowerSupplyOutputVoltage

18

PSU output voltage

PowerSupplyTemperature

19

PSU temperature

PcbTemperature

20

PCB temperature

FemAmbientTemperature

21

Thermistor mounted on sensor board in the FEM package

PasdStatus

22

SMART Box system status

LedPattern

23

Status of the service and status LEDs

FemCaseTemperature1

24

FEM 6 temperature (thermistor mounted on top of FEM case)

FemCaseTemperature2

25

FEM 12 temperature (thermistor mounted on top of FEM case)

FemHeatsinkTemperature1

26

Thermistor mounted on heatsink between FEMs 9 and 10

FemHeatsinkTemperature2

27

Thermistor mounted on heatsink between FEMs 3 and 4

PortForcings

36-47

Port forcing status for each port (“ON”, “OFF”, or “NONE”)

PortBreakersTripped

36-47

Firmware circuit breaker status for each port (True if trip has occurred)

PortsDesiredPowerOnline

36-47

Desired state of each port when FNSC is ONLINE (“OFF, “ON” or “DEFAULT”)

PortsDesiredPowerOffline

36-47

Desired state of each port when FNSC is OFFLINE (“OFF, “ON” or “DEFAULT”)

PortsPowerSensed

36-47

Power sensed status for each port (True or False)

PortsCurrentDraw

48-59

List of FEM current measurements (mA)

InputVoltageThresholds

1001-1004

High alarm, high warning, low warning and low alarm threshold values

PowerSupplyOutputVoltageThresholds

1005-1008

High alarm, high warning, low warning and low alarm threshold values

PowerSupplyTemperatureThresholds

1009-1012

High alarm, high warning, low warning and low alarm threshold values

PcbTemperatureThresholds

1013-1016

High alarm, high warning, low warning and low alarm threshold values

FemAmbientTemperatureThresholds

1017-1020

High alarm, high warning, low warning and low alarm threshold values

FemCaseTemperature1Thresholds

1021-1024

High alarm, high warning, low warning and low alarm threshold values

FemCaseTemperature2Thresholds

1025-1028

High alarm, high warning, low warning and low alarm threshold values

FemHeatsinkTemperature1Thresholds

1029-1032

High alarm, high warning, low warning and low alarm threshold values

FemHeatsinkTemperature2Thresholds

1033-1036

High alarm, high warning, low warning and low alarm threshold values

FemCurrentTripThresholds

1069-1080

12 FEM current trip thresholds (mA)

WarningFlags

10130

List of sensors in WARNING state

AlarmFlags

10132

List of sensors in ALARM state

ThresholdDifferences

Dict of the differences in thresholds between firmware and tango DB

The SMART Box PasdStatus attribute should be interpreted as follows:

PasdStatus attribute value

Meaning

OK

Initialised, system health OK

WARNING

Initialised, and at least one sensor in WARNING

ALARM

Initialised, and at least one sensor in ALARM

RECOVERY

Initialised, and at least one sensor in RECOVERY

UNINITIALISED

Not initialised, regardless of sensor states

POWERDOWN

Local tech initiated power-down sequence

SMART Box commands

The SMART Box devices support the following commands:

Command name

Arguments

Description

PowerOnPort

Port number

Request to power on the specified FEM port

PowerOffPort

Port number

Request to power off the specified FEM port

SetAntennaMasking

JSON antenna-mask dict

Set the masked status for one or more antennas (see below)

SetPortPowers

See: Setting port powers

Initialise the SMART Box and request the specified port power statuses

UpdateThresholdCache

None

Resync the threshold caches from firmware and tango database

ClearThresholdCache

None

Clear the tango DB threshold cache values

Antenna masking

SetAntennaMasking accepts a JSON string that maps antenna names to a boolean masked status, for example:

'{"sb01-01": true, "sb01-03": false}'

true means the antenna is masked — its port will not be powered on. false unmasks the antenna. Antennas absent from the dict are left unchanged, so partial updates are safe.

The command returns REJECTED if none of the supplied antenna names are known to this smartbox (e.g. all names are unrecognised, or the dict is empty). On success the port mask cache is updated immediately and the new MaskedAntennas list is persisted to the Tango database so that the masking state survives the device restarting.

Alarm recovery procedure

When the SMART Box PasdStatus attribute indicates an ALARM, WARNING or RECOVERY state, the WarningFlags and AlarmFlags attributes can be interrogated to find out which sensors have gone outside their threshold values. These registers need to be manually cleared by issuing the ResetSmartboxAlarms() and ResetSmartboxWarnings() commands after reading.

SMART Boxes automatically transition to the RECOVERY state when the relevant sensor values return to within their alarm thresholds. To return a SMART Box to an operational state after such an event, the InitializeSmartbox() command must be executed.

Setting Smartbox firmware thresholds

The attributes such as OutsideTemperatureThresholds are alarm threshold values stored in the firmware which are used internally for machine protection. To override the default values, these attributes are writeable when the device is put into ENGINEERING mode. To keep track of any overrides, when any of these values are changed they are cached in the Tango database. If a mismatch is detected between the firmware values and the Tango database (for example if the device is powered off, it will reset to the default firmware values on power up), the Smartbox device will be put into a FAULT state.

To check what values are different, read the ThresholdDifferences attribute to see the conflicts. You can then set the relevant attribute to the desired value, thus updating both the firmware and Tango database to the same value. When all conflicts have been resolved the FAULT state will be removed.

Two engineering commands are provided: UpdateThresholdCache which re-reads the database values and calculates the differences again, and ClearThresholdCache which deletes all cached values from the Tango database.

Smartbox health

The smartbox health is determined by three factors:

  1. The value of monitoring points in relation to their defined thresholds.

  2. The status as reported in the Smartbox’s SYS_STATUS register.

  3. The status of the FEM port breakers.

Threshold Evaluation Each monitoring point has four thresholds: [min_alarm, min_warning, max_warning, max_alarm]. These set on the attributes and the attributes respond by moving through tango.AttrQuality.WARNING and tango.AttrQuality.ALARM respectively dependent on monitoring point value. The healthState then reflects this as HealthState.DEGRADED -> tango.AttrQuality.WARNING and HealthState.FAILED -> tango.AttrQuality.ALARM

We can change the thresholds at run time on the smartbox by using the Tango API:

For example:

attribute_config = smartbox.get_attribute_config("InputVoltage")
alarm_config = attribute_config.alarms
alarm_config.max_warning = "49.5"
alarm_config.max_alarm = "48.5"
alarm_config.min_warning = "45.5"
alarm_config.min_alarm = "41"
attribute_config.alarms = alarm_config
smartbox.set_attribute_config(attribute_config)

We can also change the thresholds at deploy time on the smartbox through the helm charts:

ska-tango-devices:
  deviceDefaults:
    MccsSmartbox:
      InputVoltage->max_alarm: 49.5
      InputVoltage->max_warning: 48.5
      InputVoltage->min_warning: 45.5
      InputVoltage->min_alarm: 41

  devices:
    MccsSmartbox:
      low-mccs/smartbox/s8-1-sb11:
        InputVoltage->max_alarm: 51.2

Status Register Evaluation

The following translation of the Smartbox’s SYS_STATUS register values to health states is applied:

  • ‘ALARM’ or ‘RECOVERY’ indicates a health state of ‘FAILED’.

  • ‘WARNING’ indicates a health state of ‘DEGRADED’.

  • ‘UNINITIALISED’ or ‘OK’ indicates a health state of ‘OK’.

  • ‘POWERDOWN’ indicates a health state of ‘UNKNOWN’ (this state should not be used).

Port Breaker Status